Leave Your Message
Products Categories
Featured Products

6ES7141-6BG00-0AB0 DI 16x24VDC HF - Siemens SIMATIC ET 200SP Digital Input Module

Siemens 6ES7141-6BG00-0AB0
SIMATIC ET200SP DI Module
6ES7141-6BG00-0AB0 DI Module

6ES7141-6BG00-0AB0

Siemens 6ES7141-6BG00-0AB0 is a SIMATIC ET200SP DI Module with 16-channel digital input, designed for industrial automation systems, offering high reliability, compact design, and seamless integration in distributed control environments.

    SEODescription

    The Siemens 6ES7141-6BG00-0AB0 is a SIMATIC ET200SP DI Module designed for industrial automation systems, offering 16 digital input channels with 24V DC voltage compatibility. This module supports both sink and source wiring configurations, enabling flexible integration into diverse control setups. It operates within a voltage range of 20.4–28.8V DC and functions reliably in temperatures from -20°C to +60°C. As part of the ET200SP distributed I/O system, it connects directly to multiple modules via a PROFINET interface, ensuring seamless communication within PLC networks. Widely used in manufacturing, process control, and logistics, this DI Module excels in compact design and high-density signal processing. Key advantages include easy installation with push-in terminals and diagnostic capabilities, while its reliance on a separate base unit and lack of intrinsic safety certification may limit certain applications. The 6ES7141-6BG00-0AB0 DI Module is ideal for cost-effective, space-constrained automation environments requiring robust digital input solutions.

    SEOSpecification

    Parameter Specification
    Siemens 6ES7141-6BG00-0AB0 SIMATIC ET200SP DI Module
    Product Type Digital Input Module
    Number of Inputs 16
    Input Voltage 24 V DC
    Input Type Sink/Source
    Isolation 500 V AC
    Diagnostics Channel-specific
    Current Consumption 20 mA (24 V DC)
    Operating Temperature -20°C to +60°C
    Certification CE, UL, ATEX

    SEOQandA

    question:Why was the label cut off the received goods?
    answer:Labels are removed to comply with destination country regulations, prevent resale, or address intellectual property concerns.
    question:Why is a handling fee charged?
    answer:Handling fees cover bank transfer costs, administrative processing, and transaction compliance checks.
    question:What causes delayed shipments?
    answer:Delays may occur due to customs inspections, logistics issues, or documentation discrepancies.

    SEOQandA_Product

    question:Module not recognized in TIA Portal configuration.
    answer:Check module seating on Base Unit, verify firmware compatibility, and ensure correct GSD file is installed.
    question:Analog input signals show erratic readings.
    answer:Use shielded cables, ensure proper grounding, and verify sensor type matches configured measurement range.
    question:SF (System Fault) LED illuminated on module.
    answer:Check diagnostic buffer in TIA Portal for specific error codes; verify sensor connections and parameter settings.
    question:Channel-specific data not updating in PLC.
    answer:Confirm channel enable/disable settings in hardware configuration and validate address mapping in the program.
    question:Module fails PROFINET communication with controller.
    answer:Verify network topology, check PROFINET cable integrity, and validate device name/IP address assignment.