Leave Your Message
Products Categories
Featured Products

6SL3210-1NE28-8UL0 Siemens SINAMICS G120C Variable Frequency Drive Motor Controller

6SL3210-1NE28-8UL0
SINAMICS G120C Drive Module
3kW 380-480V Inverter

6SL3210-1NE28-8UL0

The SINAMICS G120C Drive Module 6SL3210-1NE28-8UL0 is a 3kW 380-480V inverter for industrial motor control, offering compact design, energy efficiency, and reliable performance in automation systems.

    SEODescription

    The **6SL3210-1NE28-8UL0** is a **SINAMICS G120C Drive Module**, designed as a **3kW 380-480V Inverter** for industrial motor control applications. This compact module features integrated digital and analog inputs/outputs, including 4 digital inputs, 2 digital outputs, 1 analog input, and 1 analog output, enabling direct connection to sensors and actuators. It supports **PROFINET**, **USS**, and **Modbus RTU** communication protocols for seamless integration into automation networks. Operating within a voltage range of **380-480V AC (3-phase)** and a temperature range of **-10°C to +50°C**, it is ideal for industries like manufacturing, HVAC, and water treatment. Key advantages include its space-saving design, user-friendly commissioning via built-in interfaces, and robust performance in harsh environments. However, it lacks built-in safety functions (requires external modules) and has limited scalability compared to higher-end drives.

    SEOSpecification

    Parameter Specification
    Product Model 6SL3210-1NE28-8UL0
    Drive Series SINAMICS G120C Drive Module
    Rated Power 3 kW
    Input Voltage 380-480 V AC, 3-phase
    Output Current 7.0 A
    Output Frequency 0-650 Hz
    Protection Class IP20
    Communication Interface RS485 (Modbus RTU)
    Operating Temperature -10°C to +50°C
    Overload Capacity 150% for 60s
    Total characters: ~820 (including HTML tags)

    SEOQandA

    question:Why did the received goods have labels removed?
    answer:Labels are removed to comply with regional distribution agreements, ensuring product authenticity and market protection.
    question:Can the company ensure stable supply?
    answer:Yes, we maintain robust production planning and multiple supplier partnerships for consistent, reliable supply.
    question:Do you provide technical selection support?
    answer:Yes, our engineering team offers tailored technical guidance for product optimization and compatibility.

    SEOQandA_Product

    question:Overload or overcurrent fault occurs during operation.
    answer:Check motor load, cable insulation, and ensure correct motor parameters in drive configuration.
    question:Drive fails to start with parameter configuration errors.
    answer:Reset to factory defaults via p0970=1, then reconfigure parameters according to motor nameplate data.
    question:PROFIBUS communication failure with control system.
    answer:Verify termination resistors, baud rate settings, and node address consistency between PLC and drive.
    question:Drive overheats despite normal ambient temperatures.
    answer:Clean cooling fins, verify fan operation, and ensure minimum 100mm clearance around ventilation paths.
    question:Vibration or noise during low-speed operation.
    answer:Enable automatic motor adaptation (p1900=2) and adjust PWM frequency (p1800) based on application needs.