Leave Your Message
Products Categories
Featured Products

DRT2-ID04CL-1 4-Ch Input Module - Omron DRT2 Series Digital Sensor Interface | Industrial I/O Device

DRT2-ID04CL-1 DeviceNet Module
DRT2-ID04CL-1 I/O Terminal
DRT2-ID04CL-1 Digital Input

DRT2-ID04CL-1

DRT2-ID04CL-1 DeviceNet Module is a compact I/O Terminal with 4-channel Digital Input for industrial automation networks.

    SEODescription

    The DRT2-ID04CL-1 DeviceNet Module is a compact I/O Terminal designed for industrial automation, featuring 4 digital input channels (24V DC sinking type) to interface with sensors and switches. It operates as a DeviceNet slave unit, supporting direct connection to up to 64 nodes via a CAN-based communication interface with baud rates up to 500 kbps. The module operates within a 24V DC ±10% voltage range and withstands temperatures from -25°C to 55°C, making it suitable for harsh environments in manufacturing, automotive, and machinery sectors. Its key advantages include plug-and-play simplicity, robust noise immunity, and DIN rail mounting compatibility. However, it lacks output functionality and requires a separate DeviceNet master for network integration. The DRT2-ID04CL-1 Digital Input module excels in centralized data acquisition systems requiring reliable sensor signal processing.

    SEOSpecification

    Parameter Specification
    DeviceNet Module Model DRT2-ID04CL-1
    I/O Terminal Type Digital Input Module
    Input Channels 4 points (Sink/Source selectable)
    Rated Input Voltage DC 24V
    Operating Voltage Range DC 12-24V ±10%
    Input Current 3mA @ DC 24V (per point)
    Response Time 1ms max (ON/OFF delay)
    Connection Type DeviceNet open-type 5-pin connector
    Compatible Network DeviceNet (CAN protocol)
    Isolation Method Photocoupler isolation
    Operating Temperature -25°C to 55°C
    Weight 150g max

    SEOQandA

    question:Can you provide shipment photos and purchase dates for similar products?
    answer:Yes, upon request. Please contact us in advance for specific details.
    question:What shipping methods do you support?
    answer:We support DHL, Fedex, UPS, and other major carriers. Tracking info provided.
    question:Why did the received items have labels removed?
    answer:Labels might be removed due to customs inspection or brand policies. Contact us for assistance.

    SEOQandA_Product

    question:DRT2-ID04CL-1 input signals not detected. Possible causes?
    answer:Check wiring connections, verify sensor compatibility (NPN/PNP), ensure power supply matches specifications, and confirm PLC configuration settings.
    question:DRT2-ID04CL-1 communication failure with PLC. How to resolve?
    answer:Verify DeviceNet node address settings, inspect communication cables for damage, and ensure proper termination resistors are installed on the network.
    question:DRT2-ID04CL-1 input LED indicators remain off. What to check?
    answer:Confirm input voltage levels meet 12-24VDC range, test sensors independently, and inspect for wiring shorts or open circuits in input channels.
    question:DRT2-ID04CL-1 shows erratic behavior after installation. Solutions?
    answer:Check for electrical noise interference, ensure proper grounding, verify power supply stability, and confirm module firmware is up-to-date.
    question:DRT2-ID04CL-1 fails to respond during device replacement. Troubleshooting steps?
    answer:Verify identical model replacement, confirm configuration data transfer, check connector seating, and validate network parameters match original setup.