FX3U-4DA-ADP Analog Output Module, Mitsubishi FX3U Series 4-Channel DAC Expansion Board

FX3U-4DA-ADP module
Mitsubishi FX3U analog
4-channel ADP output

FX3U-4DA-ADP

The FX3U-4DA-ADP module is a Mitsubishi FX3U analog expansion unit providing 4-channel ADP output for voltage/current signal control, designed for seamless integration in industrial automation systems requiring precise analog output capabilities.

    SEODescription

    The Mitsubishi FX3U-4DA-ADP module is a compact 4-channel ADP output expansion unit designed for the FX3U series PLCs, delivering high-precision analog control in industrial automation. This module directly connects to the FX3U main unit via its built-in extension port, requiring no additional communication interfaces. It supports voltage (±10V) or current (4–20mA/0–20mA) outputs across all four channels with 12-bit resolution, enabling precise process control in applications like temperature regulation, motor speed control, and pressure management. Operating at 24V DC within 0–55°C, it suits harsh manufacturing and machinery environments. Key advantages include plug-and-play installation, minimal wiring, and seamless FX3U integration, though it lacks isolated outputs and relies entirely on the host PLC for configuration via GX Works2 software. Its compact design optimizes panel space in control cabinets.

    SEOSpecification

    Parameter Specification
    Module Name FX3U-4DA-ADP
    Compatible PLC Series Mitsubishi FX3U analog expansion
    Output Type Analog voltage/current
    Channels 4-channel ADP output
    Resolution 16-bit (0-4095)
    Output Range 0-10V DC, ±10V DC, 4-20mA
    Output Isolation Non-isolated
    Power Supply 5V DC (from PLC)
    Mounting Direct FX3U side connection
    Operating Temp. 0-55°C
    Storage Temp. -25-75°C
    Dimensions 55 x 90 x 87 mm
    Weight 0.3 kg

    SEOQandA

    question:How is the after-sales service handled if a refurbished product malfunctions?
    answer:We offer replacement or refund per warranty terms, provided the issue is confirmed as refurbishment-related.
    question:Why was the product received with removed branding labels?
    answer:Labels are removed to prevent unauthorized resale, as per distribution agreements. Product functionality remains unaffected.
    question:Do you provide technical selection support?
    answer:Yes, we offer free technical consultation to help you choose the most suitable product for your needs.

    SEOQandA_Product

    question:FX3U-4DA-ADP output signal inaccuracy
    answer:Check wiring integrity, ensure proper grounding/shielding. Recalibrate using offset/gain adjustment via GX Works2.
    question:FX3U-4DA-ADP not recognized by PLC
    answer:Verify module installation order - must be adjacent to main unit. Confirm power supply meets 24VDC±10% requirement.
    question:Incorrect output range configuration
    answer:Validate BFM parameters (BFM#0) match selected voltage (0-10V/±10V) or current (4-20mA/0-20mA) mode via TO instruction.
    question:No output from specific channel
    answer:Check channel enable bits (BFM#1). Confirm CH1-CH4 activation status and verify TO command writes correct data to BFM#5-BFM#8.
    question:Module overheating or abnormal noise
    answer:Inspect output load for short circuits. Ensure total current