Leave Your Message
Products Categories
Featured Products

FX3U-4LC Mitsubishi MELSEC FX Series Temperature Control Module, 4-Channel PID Controller Thermocouple Input

FX3U-4LC
Mitsubishi FX3U-4LC Module
4-Channel Temperature Control

FX3U-4LC

The Mitsubishi FX3U-4LC Module is a 4-channel temperature control solution for precise regulation in industrial automation systems, supporting thermocouples and RTDs with PID functionality.

    SEODescription

    The Mitsubishi FX3U-4LC Module is a 4-Channel Temperature Control module designed for precise regulation in industrial automation systems. Integrated with the FX3U series PLCs, it supports four independent channels compatible with thermocouples (K, J, R, S, E, T, N, PLII, U) or RTD sensors (Pt100, JPt100), enabling simultaneous monitoring and control of heating or cooling devices via transistor or relay outputs. The module operates on 24 VDC power and functions within a temperature range of 0–55°C, ensuring reliability in harsh environments. It communicates via the FX3U PLC's built-in RS-422/USB interface and supports PID control algorithms for optimized thermal stability. Ideal for industries like food processing, plastics manufacturing, and chemical plants, the FX3U-4LC offers compact integration and high accuracy. However, its dependency on the host PLC for programming and limited standalone functionality may require additional system configuration.

    SEOSpecification

    Parameter Specification
    Model FX3U-4LC
    Module Type Mitsubishi FX3U-4LC Module
    Control Channels 4-Channel Temperature Control
    Input Type Thermocouple (K/J/R/S/E/T) / Platinum Resistor (Pt100)
    Temperature Range -100°C to 1300°C (K-type), -200°C to 600°C (Pt100)
    Resolution 0.1°C / 0.1°F
    Control Method PID / ON-OFF Control
    Output Type Transistor (2 outputs per channel) / Relay (optional)
    Communication Interface RS-422/485 (Built-in)
    Power Supply 24V DC ±10% (50mA)
    Mounting DIN Rail or Screw Mounting
    Operating Temperature 0°C to 55°C
    Dimensions 90mm (W) × 87mm (H) × 90mm (D)

    SEOQandA

    question:Why choose us?
    answer:Asia's top industrial automation trader with 20 years' experience. Guaranteed quality, strong reputation, 85% clients are repeats.
    question:Do you accept payment after delivery?
    answer:Standard prepayment required. Flexible terms for long-term partners with proven credit history.
    question:How handle refurbished product failures?
    answer:Immediate free repair/replacement within warranty, even if refurbished found. Full accountability for product integrity.

    SEOQandA_Product

    question:How to resolve incorrect temperature readings on FX3U-4LC?
    answer:Verify sensor wiring matches the manual and ensure correct sensor type is selected in parameter settings.
    question:Why does FX3U-4LC fail to communicate with the PLC?
    answer:Check DIP switch settings for correct module address and validate FROM/TO instruction addressing in the program.
    question:How to stabilize erratic temperature control with FX3U-4LC?
    answer:Adjust PID parameters (P, I, D) via configuration software and increase sampling cycle if noise is present.
    question:What causes the ERROR LED to light on FX3U-4LC?
    answer:Check error code via diagnostic function; common causes include sensor disconnection or input range exceedance.
    question:Why does FX3U-4LC show wrong sensor type data?
    answer:Reconfigure the input type via parameter mode (e.g., K/J/T for thermocouples, Pt100 for RTD) to match the sensor.